V2H Bidirectional EV Feeder Wire Sizer
Calculate continuous 125% overcurrent protection, minimum conductor gauge, and inverter export voltage rise to prevent IEEE 1547 grid-tied and island overvoltage trips in Vehicle-to-Home (V2H) systems.
NEC 625 & IEEE 1547 Governing Rules: Vehicle-to-Home (V2H) bidirectional EVSEs operate as continuous loads during charging and continuous generation sources during backup power export. Under NEC 625.41 & 625.42, branch-circuit conductors and breakers must be sized for at least 125% of maximum continuous current ($I_{\text{design}} = I_{\text{nameplate}} \times 1.25$). Under IEEE 1547 / UL 1741, feeder export voltage rise should not exceed 1.5% (3.6V on 240V) to prevent premature high-voltage inverter shutoffs ($V_{\text{grid}} \ge 252\text{V}$).
EVSE Hardware & Feeder Parameters
Feeder Specification & Export Voltage Metrics
Click Calculate Feeder Sizing to compute continuous protection ratings, wire gauge, and IEEE 1547 voltage rise headroom.
Governing Continuous Ampacity & Export Voltage Rise Formulas
Commercial V2H / V2G Hardware Feeder Requirements
Manufacturer continuous amperage, minimum NEC breaker ratings, and recommended feeder conductors.
| Hardware / Vehicle Platform | Continuous Current | Continuous kW | Min NEC Breaker (125%) | Min Copper Conductor (NEC 310.16) | Upsized for Distance (>50 ft) |
|---|---|---|---|---|---|
| Ford Charge Station Pro (F-150 Lightning) | 80 Amps | 19.2 kW | 100 Amps | 3 AWG Cu (100A) | 2 AWG / 1 AWG Cu |
| Tesla Universal Wall Connector (Powershare) | 48 Amps | 11.5 kW | 60 Amps | 6 AWG Cu (65A) | 4 AWG Cu |
| Enphase IQ Bidirectional EV Charger | 48 Amps | 11.5 kW | 60 Amps | 6 AWG Cu (65A) | 4 AWG Cu |
| Wallbox Quasar 2 (Kia EV9 / Genesis) | 40 Amps | 9.6 kW | 50 Amps | 8 AWG Cu (50A) | 6 AWG Cu |
| Commercial Fleet CCS V2G Station | 120 Amps | 28.8 kW | 150 Amps | 1/0 AWG Cu (150A) | 2/0 AWG / 3/0 AWG Cu |
Step-by-Step Worked Engineering Example
80-Amp Ford Charge Station Pro (19.2 kW V2H Backup)
Installation Context: A homeowner installs an 80-amp Ford Charge Station Pro to provide emergency microgrid backup power from an F-150 Lightning extended-range battery pack. The EVSE is mounted in a detached garage 65 feet from the home backup interface switch.
- Calculate NEC 625.41 Continuous Overcurrent Protection: $$I_{\text{breaker}} = 80\text{ A} \times 1.25 = 100\text{ Amperes}$$ A 100A 2-pole circuit breaker must be installed in the backup distribution panel.
- Select Minimum Conductor Ampacity per NEC Table 310.16: At 75°C terminal ratings, 3 AWG copper carries 100A, exactly matching the 100A requirement.
- Calculate Inverter Export Voltage Rise on 3 AWG Copper: For 3 AWG copper, resistance is $0.245\,\Omega\text{ per }1000\text{ ft}$. Total loop length is $65\text{ ft} \times 2 = 130\text{ ft}$. $$R_{\text{loop}} = (130 / 1000) \times 0.245 = 0.03185\,\Omega$$ $$\Delta V_{\text{rise}} = 80\text{ A} \times 0.03185\,\Omega = 2.55\text{ Volts } (1.06\%)$$ Terminal voltage at full 80A export: $240.0\text{V} + 2.55\text{V} = 242.55\text{ Volts}$.
- Evaluate Voltage Rise with Upsized 1 AWG Copper: 1 AWG copper has $R = 0.154\,\Omega\text{ per }1000\text{ ft}$. $$R_{\text{loop}} = (130 / 1000) \times 0.154 = 0.0200\,\Omega$$ $$\Delta V_{\text{rise}} = 80\text{ A} \times 0.0200\,\Omega = 1.60\text{ Volts } (0.67\%)$$ Terminal voltage is restricted to $241.60\text{V}$, providing ample headroom below the $252.0\text{V}$ IEEE 1547 high-voltage trip limit and eliminating inverter nuisance shutdowns.