Equipment Grounding Conductor (EGC) & CPC Sizer

Determine minimum safety ground conductor sizes for AC and DC circuits per NEC Table 250.122 and BS 7671 Table 54.7 / Adiabatic Equation. Calculates proportional ground upsizing when phase conductors are enlarged for voltage drop.

💡 Sizing Phase or Supply Conductors? Size your hot and neutral power conductors with our DC Wire Size Calculator and diagnostic Voltage Drop Calculator.

⚡ Quick Engineering Answer: How Is Ground Wire Sized?

NEC 250.122 • BS 7671

An Equipment Grounding Conductor (EGC) is sized based on the rating of the upstream circuit breaker or fuse protecting the circuit, NOT the operating load current. Under NEC Table 250.122, a 20A breaker requires a 12 AWG copper (10 AWG aluminum) ground; a 60A breaker requires 10 AWG copper; and a 200A breaker requires 6 AWG copper (4 AWG aluminum). Crucially, under NEC 250.122(B), if phase conductors are upsized to reduce voltage drop on long runs, the ground wire must be proportionally enlarged in circular mils by the same ratio so fault current impedance does not rise. Under BS 7671, CPC size is verified using the adiabatic equation ($S = \sqrt{I^2 t} / k$).

⚡ 1-Click Circuit Presets Load standard branch, feeder, and service protection sizes
Overcurrent Device & Circuit Parameters
Overcurrent Protection Device (OCPD) ampere rating.
Standard NEC Table 250.122 material basis.
Minimum Required Ground Conductor Size
12 AWG Copper (3.31 mm²)
NEC Table 250.122 Standard Sizing • 6,530 Circular Mils
OCPD Breaker / Fuse Rating 20 Amps
Conductor Material Annealed Copper
UK / IEC CPC Equivalent 2.5 mm² to 4 mm² CPC
NEC 250.122(B) Status Standard (No Upsizing)
NEC Table 250.122 Minimum Specification: A minimum 12 AWG copper Equipment Grounding Conductor matches published Table 250.122 sizing for a 20A overcurrent device.
🛠 Companion Grounding & Protection Tools Safety Suite

Complete your electrical grounding and circuit protection design:

NEC Table 250.122: Minimum Size Equipment Grounding Conductors

Official Code Reference • NFPA 70 National Electrical Code

The table below lists the minimum size Equipment Grounding Conductors for grounding raceways and equipment based on the rating or setting of the upstream automatic overcurrent device in the circuit ahead of equipment.

Rating of Overcurrent Device (Amperes) Copper Conductor (AWG or kcmil) Aluminum / Copper-Clad Aluminum Metric Cross-Section (mm²)
15 A 14 AWG 12 AWG 2.08 mm²
20 A 12 AWG 10 AWG 3.31 mm²
30 A 10 AWG 8 AWG 5.26 mm²
40 A • 60 A 10 AWG 8 AWG 5.26 mm²
100 A 8 AWG 6 AWG 8.37 mm²
200 A 6 AWG 4 AWG 13.3 mm²
300 A 4 AWG 2 AWG 21.2 mm²
400 A 3 AWG 1 AWG 26.7 mm²
500 A 2 AWG 1/0 AWG 33.6 mm²
600 A 1 AWG 2/0 AWG 42.4 mm²
800 A 1/0 AWG 3/0 AWG 53.5 mm²
1000 A 2/0 AWG 4/0 AWG 67.4 mm²

Frequently Asked Questions: Ground Wire & CPC Sizing

How does NEC Table 250.122 determine minimum equipment grounding conductor size?

NEC Table 250.122 establishes minimum Equipment Grounding Conductor (EGC) copper and aluminum wire sizes based on the ampere rating of the upstream circuit breaker or fuse. For example, a 15A or 20A breaker specifies 14 AWG or 12 AWG copper, a 60A breaker requires 10 AWG copper, and a 100A breaker requires 8 AWG copper (or 6 AWG aluminum). If phase conductors are upsized for voltage drop per NEC 250.122(B), the ground conductor must be upsized proportionally in circular mils.

Why must ground conductors be upsized when phase wires are enlarged?

When phase conductors are upsized to counteract voltage drop over long distances, the impedance of the supply conductor decreases. If the equipment grounding conductor is left at the standard code minimum size, the return path retains high impedance. During a line-to-ground fault, the elevated ground path resistance can reduce fault current below the instantaneous trip threshold of the circuit breaker, delaying clearing time and creating hazardous touch voltages on metal equipment frames (NEC 250.122(B)).

How does the BS 7671 adiabatic equation size a CPC?

In British Standard BS 7671, Regulation 543.1.3 allows Circuit Protective Conductors to be sized using the adiabatic equation: S = sqrt(I^2 * t) / k, where S is the minimum conductor cross-section in mm², I is the prospective fault current in Amperes, t is the operating disconnection time of the protective device in seconds (typically 0.1 to 0.4s), and k is a material constant (115 for 70°C PVC copper, 143 for 90°C XLPE copper).

Can bare copper wire be used as an Equipment Grounding Conductor?

Yes. NEC allows Equipment Grounding Conductors to be bare, covered, or insulated. When insulated, the conductor must have a continuous green outer finish or green with one or more yellow stripes per NEC 250.119.