Heat Pump LRA Soft Starter & Generator Sizer
Calculate compressor Locked Rotor Amps (LRA) inrush reduction, size electronic soft starters, and determine the exact minimum backup generator and off-grid inverter surge capacity.
Compressor Inrush Physics: Single-phase residential heat pump compressors draw 5× to 7× Rated Load Amps (RLA) at startup, causing massive voltage dips on backup power systems. An advanced microprocessor soft starter (e.g. Micro-Air EasyStart, ICM, Hyper Engineering) ramps voltage across the first 100–250 ms, achieving a 65% to 75% reduction in starting surge ($I_{\text{start}} = \text{LRA} \times 0.30$). This enables a 3-ton to 4-ton heat pump to start cleanly on an 8 kW off-grid inverter or a 7.5 kW generator.
Compressor Nameplate Specifications
Surge Reduction & Power Source Sizing
Click Calculate Soft Start Surge to evaluate inrush current reduction and minimum power source requirements.
Compressor Inrush & Power Source Sizing Formulas
Residential Compressor Inrush vs Soft Starter Benchmark Table
Across-the-line Locked Rotor Amps compared to 70% soft starter inrush reduction across standard tonnages.
| Compressor Tonnage | Typical RLA (Amps) | Nameplate LRA | Raw Surge @ 240V | Soft Start Surge (70%) | Soft Start Power | Min Sized Generator |
|---|---|---|---|---|---|---|
| 1.5 Ton | 9.0 A | 48.0 A | 11.5 kW | 14.4 A | 3.46 kW | 4.5 kW / 5.5 kW Surge |
| 2.0 Ton | 11.2 A | 58.0 A | 13.9 kW | 17.4 A | 4.18 kW | 5.5 kW / 6.5 kW Surge |
| 2.5 Ton | 13.5 A | 67.0 A | 16.1 kW | 20.1 A | 4.82 kW | 6.5 kW / 7.5 kW Surge |
| 3.0 Ton | 14.7 A | 79.0 A | 19.0 kW | 23.7 A | 5.69 kW | 7.5 kW / 9.0 kW Surge |
| 3.5 Ton | 17.9 A | 96.0 A | 23.0 kW | 28.8 A | 6.91 kW | 8.5 kW / 10.5 kW Surge |
| 4.0 Ton | 19.8 A | 109.0 A | 26.2 kW | 32.7 A | 7.85 kW | 9.5 kW / 11.5 kW Surge |
| 5.0 Ton | 24.3 A | 134.0 A | 32.2 kW | 40.2 A | 9.65 kW | 12.0 kW / 14.5 kW Surge |
Step-by-Step Worked Engineering Example
3.0-Ton Heat Pump Compressor on Off-Grid Solar Backup
Installation Context: A homeowner with a 3.0-ton central heat pump wants to run heating and cooling during power outages from an off-grid solar battery system. The outdoor unit data tag specifies RLA = 14.7A and LRA = 79.0A at 240V AC.
- Calculate Raw Across-the-Line Starting Inrush: $$P_{\text{raw}} = 79.0\text{ A} \times 240\text{ V} = 18,960\text{ Watts } (19.0\text{ kW})$$ Without soft start, this instantaneous 19 kW pulse exceeds the surge limit of standard residential 8 kW to 10 kW inverters, causing instantaneous overload shutdown.
- Calculate Soft Starter Reduced Inrush Current (70% Reduction): $$I_{\text{soft}} = 79.0\text{ A} \times (1.0 - 0.70) = 79.0 \times 0.30 = 23.70\text{ Amperes}$$ The electronic soft starter limits peak current to just 23.7A during the initial 150 ms voltage ramp.
- Calculate Soft Starter Surge Wattage: $$P_{\text{surge,soft}} = 23.70\text{ A} \times 240\text{ V} = 5,688\text{ Watts } (5.69\text{ kW})$$
- Size Backup Generator and Solar Inverter: - **Generator:** Adding a 25% safety buffer for engine governor response gives $5.69\text{ kW} \times 1.25 = 7.11\text{ kW}$. A standard **7.5 kW running / 9.0 kW surge generator** easily handles startup without bogging down. - **Solar Inverter:** The system requires at least $5.7\text{ kVA}$ surge capacity. A single **8 kW hybrid inverter (with 12 kVA 10-second surge)** or dual stacked 5 kW inverters will easily start the compressor while powering household base loads.