Rooftop Solar PV Conduit Thermal Ampacity Derater

Calculate derated solar DC cable ampacity by compounding outdoor ambient design temperatures (NEC 310.15(B)(1)), rooftop conduit distance thermal adders (NEC Table 310.15(B)(2)), and conductor bundling fill factors.

Quick Engineering Standard: Compounded Rooftop Thermal Derating

NEC 310.15 • NEC 310.16 • NEC 690.8

Rooftop solar DC conductors experience extreme thermal stress where outdoor air temperature, radiant roof heat, and bundled electrical resistance combine. Under NEC Table 310.15(B)(2), conduit installed within 0.5 inches of a dark roof incurs a +33°C (+60°F) adder, elevating internal conduit temperatures past 65°C to 75°C on a standard summer day. When compounded with a 0.80 bundling factor for 4 to 6 conductors, a 10 AWG 90°C copper wire rated for 40A in free air is derated by over 50% to just 18.5A to 20.8A. Elevating the conduit at least 3.5 inches above the roof surface saves up to 15°C of heat, often eliminating the need to upsize to 8 AWG wire.

Raceway & String Design Inputs

Base ampacity from NEC Table 310.16 (90°C column).
ASHRAE 2% summer design dry bulb temperature (e.g. 35°C to 42°C).
NEC Table 310.15(B)(2) rooftop distance thermal adder.
NEC Table 310.15(C)(1) conduit fill bundling factor.
Panel nameplate short-circuit current (Isc).

Derated Ampacity & NEC 690 Compliance

Effective Conduit Temperature
-- °C
Ambient + rooftop height adder
Combined Derating Factor
-- %
Temp factor × bundling factor
Allowable Derated Ampacity
-- A
Net continuous carrying capacity
NEC 690.8 Max Circuit Current
-- A
1.25 × Isc required threshold

NEC 690.8 Compliance & Installation Assessment

Select parameters and click Calculate to evaluate rooftop thermal derating.

Governing NEC Rooftop Derating Formulas

Rooftop raceway sizing requires compounding two distinct derating multipliers against base ampacity:

Effective Internal Conduit Temperature (Teffective)
Teffective = Tambient_design + ΔTrooftop_adder
ΔTrooftop_adder is derived from NEC Table 310.15(B)(2). A 38°C summer day with conduit within 0.5" to 3.5" of the roof (+22°C adder) results in a 60°C operating environment inside the raceway.
Net Derated Allowable Ampacity (Iallowable)
Iallowable = Ibase_table310.16 × CFtemp × CFbundling
Where CFtemp is from NEC Table 310.15(B)(1) (e.g. 0.71 at 60°C for 90°C wire) and CFbundling is from NEC Table 310.15(C)(1) (e.g. 0.80 for 4 to 6 conductors).
NEC 690.8 Conductor Sizing Criteria
Condition 1: Iallowable_derated ≥ 1.25 × Isc  |  Condition 2: Ibase_underated ≥ 1.25 × 1.25 × Isc
The derated conductor must carry the 125% maximum circuit current, while the base un-derated conductor must carry the 125% continuous duty multiplier.

Empirical NEC Rooftop Distance & Thermal Adder Matrix

Reference table showing the thermal adders, temperature correction factors (90°C rated wire), and resulting derated ampacity for 10 AWG copper wire across various roof elevations:

Conduit Height Above Roof Surface NEC Thermal Adder Eff. Temp @ 35°C Ambient Temp Factor (90°C Wire) 4–6 Cond. Factor 10 AWG Allowable Ampacity (Base 40A)
On Roof / < 0.5 in (< 13 mm) +33°C (+60°F) 68°C (154°F) 0.58 0.80 18.5 Amperes (-53.8%)
0.5 in to 3.5 in (13 mm to 90 mm) +22°C (+40°F) 57°C (135°F) 0.71 0.80 22.7 Amperes (-43.2%)
3.5 in to 12 in (90 mm to 300 mm) +17°C (+30°F) 52°C (126°F) 0.76 0.80 24.3 Amperes (-39.2%)
12 in to 36 in (300 mm to 900 mm) +14°C (+25°F) 49°C (120°F) 0.82 0.80 26.2 Amperes (-34.5%)
> 36 in / Ground-Mounted 0°C (0°F) 35°C (95°F) 0.96 0.80 30.7 Amperes (-23.2%)

Worked Engineering Walkthrough: 2-String 10 AWG Rooftop Run

1
Determine Base Conductor Ampacity & Maximum Current:

Two parallel strings of PV modules with $I_{sc} = 11.5\text{A}$ are routed through a single rooftop EMT conduit using 10 AWG THHN copper wire. Base ampacity from NEC Table 310.16 (90°C column) is $40.0\text{ Amperes}$. Maximum circuit current per NEC 690.8 is:

I_max = 1.25 * 11.5A = 14.38 Amperes.
2
Calculate Compounded Deratings (Temperature + Rooftop + Bundling):

The outdoor summer design temperature is $38^\circ\text{C}$. The EMT conduit is mounted on rooftop strut blocks $1.5\text{ inches}$ above the shingles ($+22^\circ\text{C}$ adder per NEC Table 310.15(B)(2)). Total effective internal temperature is:

T_effective = 38°C + 22°C = 60°C.

At 60°C, the temperature correction factor for 90°C rated wire is $CF_{temp} = 0.71$. Because the two strings require 4 current-carrying conductors (2 positive, 2 negative), the bundling adjustment factor from NEC Table 310.15(C)(1) is $CF_{bundle} = 0.80$. The net allowable derated ampacity is:

I_allowable = 40.0A * 0.71 * 0.80 = 22.72 Amperes.
3
Verify NEC 690.8 Compliance:

Condition 1: $I_{allowable} = 22.72\text{A} \ge I_{max} = 14.38\text{A}$ (PASSED with a 58% safety margin).

Condition 2: $I_{base} = 40.0\text{A} \ge 1.5625 \times 11.5\text{A} = 17.97\text{A}$ (PASSED). 10 AWG wire satisfies all governing NEC requirements.